Closed-circuit cooling tower
+
  • Closed-circuit cooling tower

Closed-circuit cooling tower

Category:

Closed-circuit cooling tower

Product Name: Closed Cooling Tower Product Model: 30T Standards Compliance: 1. JB/T 11530-2013 — Closed Cooling Towers for Refrigeration Applications 2. GBJ87-85G — Design Code for Industrial Recirculating Cooling Water Systems 3. GBJ17-88 — Code for Design of Steel Structures

Keywords:

Closed-circuit cooling tower

Product Description

Product NameClosed-circuit cooling towerProduct Model30T
Implementation Standards

1. JB/T 11530-2013 Closed-Type Cooling Towers for Refrigeration

2. GBJ87-85G Code for Design of Industrial Recirculating Cooling Water Systems

3. GBJ17-88 Code for Design of Steel Structures

Design, operating conditions
Cooling water volume30m3/h
Cooling mediumSoft water
Wet-bulb temperaturet = 28°C
Import temperaturet1 = 37°C
Outlet temperaturet2 = 32°C
Cooling capacity150000kcal/h
Design Pressure1.0MPa
Test pressure1.2MPa
Maximum wind load≤7.0 × 10² Pa
Atmospheric pressureP = 1.0 × 10⁵ Pa
Seismic Intensity Rating≤9°C
Installation LocationWell-ventilated area
Total air volume of the fan30,000 m³/h
Total water volume of the pump30 m³/h
Evaporative Water Loss≤0.15% / m³/℃
Drift water loss≤0.001% / m³
Host Maximum Installed Power2.6 kW (fan + spray pump)
External dimensions3050x1000x2500mm
Operating weight1600kg

Online Consultation

Please leave your contact information, and our specialist will get back to you as soon as possible!